Sort
Profile photo for Assistant
Assistant

Transformer impedance is often expressed in percentage to provide a standardized way of comparing the relative impedance of different transformers regardless of their power ratings. Here are the main reasons for using percentage impedance:

  1. Standardization: By expressing impedance as a percentage, it allows for easy comparison between transformers of different sizes and ratings. For example, a transformer with a 5% impedance will behave similarly in terms of voltage drop and short-circuit current characteristics to another transformer with a 5% impedance, regardless of their kVA ratings.
  2. Voltage

Transformer impedance is often expressed in percentage to provide a standardized way of comparing the relative impedance of different transformers regardless of their power ratings. Here are the main reasons for using percentage impedance:

  1. Standardization: By expressing impedance as a percentage, it allows for easy comparison between transformers of different sizes and ratings. For example, a transformer with a 5% impedance will behave similarly in terms of voltage drop and short-circuit current characteristics to another transformer with a 5% impedance, regardless of their kVA ratings.
  2. Voltage Regulation: The percentage impedance directly relates to the voltage drop across the transformer under load conditions. A transformer with a 5% impedance will have a 5% voltage drop at full load, which helps engineers understand how much the output voltage will decrease when the transformer is supplying its rated load.
  3. Short-Circuit Current Calculation: The percentage impedance is crucial for calculating short-circuit currents. A lower percentage impedance means higher short-circuit currents, which is important for designing protective devices and ensuring system stability.
  4. Ease of Use: Using a percentage simplifies the calculations involved in power systems. Engineers can easily incorporate impedance values into their calculations without needing to convert them into ohms or other units that depend on the transformer's power rating.

Calculation of Percentage Impedance

The percentage impedance ([math]Z_{\%}[/math]) can be calculated using the formula:

[math]Z_{\%} = \left( \frac{Z}{Z_{base}} \right) \times 100[/math]

Where:
-
[math]Z[/math] is the actual impedance in ohms.
-
[math]Z_{base}[/math] is the base impedance, which can be calculated from the transformer's rated power and voltage.

In summary, representing transformer impedance as a percentage is a practical method that enhances clarity and consistency in electrical engineering applications, particularly in power system analysis and design.

Profile photo for Mohamed Rafeequdin

Thanks for the A2A.

It is the most concise way of expressing regulation of the transformer.

Let me explain.

suppose I tell you that a 1-phase transformer has X=110 ohms and negligible R, next you will ask me what is the KVA rating, say 990 KVA, then you will ask me about the voltages, say, 33/11 kV.

Then you will ask me as to which side this X refers to , say 33 kV side.

Now, after all these clarificat

Thanks for the A2A.

It is the most concise way of expressing regulation of the transformer.

Let me explain.

suppose I tell you that a 1-phase transformer has X=110 ohms and negligible R, next you will ask me what is the KVA rating, say 990 KVA, then you will ask me about the voltages, say, 33/11 kV.

Then you will ask me as to which side this X refers to , say 33 kV side.

Now, after all these clarifications, you find the rated currents on 33 kV side as 30 A and on 11 kV side as 90 A.

Then you will find X11=X referred to 11 kV side = [(11/33)^2]110= 12.22 ohms

Then at rated load you find voltage drop on 33 kV side is 110x30=3300 V <== (i.e., 10% of 33 kV)

Then at rated load you find voltage drop on 11 kV side is 12.22x90=1100 V <=== (i.e., 10% ...

Profile photo for Fiverr

The best freelance digital marketers can be found on Fiverr. Their talented freelancers can provide full web creation, or anything Shopify on your budget and deadline. If you’re looking for someone who can do Magento, Fiverr has the freelancers qualified to do so. If you want to do Dropshipping, PHP, or, GTmetrix, Fiverr can help with that too. Any digital marketing help you need Fiverr has freelancers qualified to take the reins. What are you waiting for? Start today.

Profile photo for Noufal Riyas

Impedance(Z) = Resistance(R) + j Reactance(X)

  • Percentage Resistance is the resistance drop in volts at rated current and frequency as a percentage of the rated voltage.
    • %R = ( IR/V)*100
  • Percentage Reactance is the reactance drop in volts at rated current and frequency as a percentage of the rated voltage.
    • %X = ( IX/V)*100
  • Percentage impedance is nothing but a measure of the volt drops when the transformer in on full load due to the winding resistancevand leakage reactance expressed as a percentage of the rated voltage.
    • %Z = ( IZ/V)*100
  • The important advantages of expressing resistance and reactance o

Impedance(Z) = Resistance(R) + j Reactance(X)

  • Percentage Resistance is the resistance drop in volts at rated current and frequency as a percentage of the rated voltage.
    • %R = ( IR/V)*100
  • Percentage Reactance is the reactance drop in volts at rated current and frequency as a percentage of the rated voltage.
    • %X = ( IX/V)*100
  • Percentage impedance is nothing but a measure of the volt drops when the transformer in on full load due to the winding resistancevand leakage reactance expressed as a percentage of the rated voltage.
    • %Z = ( IZ/V)*100
  • The important advantages of expressing resistance and reactance of a transformer in percentage is that the percentage resistance and percentage reactance have same values whether determined referred to primary or secondary whereas expressed in ohms they have different values when referred to primary and secondary.
  • Further, the percentage reactance and percentage impedance are convenient for computing the current that will flow in a transformer when the secondary is accidentally shorted.

-> Short circuit current = ( 100/percent impedance )*Full load rated current

Profile photo for Shashi Ranjan Mishra

The percentage of a transformer can be described as the percentage of the nominal voltage in the primary that is required to circulate the rated current in the secondary.

Short-circuit test is used to determine percentage impedance. In Short Circuit test the secondary of the transformer whose percentage impedance is to be measured is shorted. The voltage on the primary is gradually increased from zero till the secondary current reaches the transformer's rated value.

The percentage impedance of the transformer is calculated as

Z%= (Impedance Voltage/Rated Voltage)*100

Thus a transformer with a

The percentage of a transformer can be described as the percentage of the nominal voltage in the primary that is required to circulate the rated current in the secondary.

Short-circuit test is used to determine percentage impedance. In Short Circuit test the secondary of the transformer whose percentage impedance is to be measured is shorted. The voltage on the primary is gradually increased from zero till the secondary current reaches the transformer's rated value.

The percentage impedance of the transformer is calculated as

Z%= (Impedance Voltage/Rated Voltage)*100

Thus a transformer with a primary rating of 110V which requires a voltage of 10V to circulate the rated current in the short-circuited secondary would have an impedance of 9%.

Profile photo for Quora User
  • Percentage impedance of a transformer is the percentage of primary voltage required to be offered at one terminal, in order to ensure circulation of full load current at the other terminal.
  • In an interconnected power system with many voltage levels, transformers are major equipment as they act as junctions between two indifferent system voltage levels.
  • For the analysis of such power system networks, transformer impedences are a primary requirement.
  • The equivalent impedence of a transformer is not equal for two different voltage levels. Thus, for a power system network with two or more voltage lev
  • Percentage impedance of a transformer is the percentage of primary voltage required to be offered at one terminal, in order to ensure circulation of full load current at the other terminal.
  • In an interconnected power system with many voltage levels, transformers are major equipment as they act as junctions between two indifferent system voltage levels.
  • For the analysis of such power system networks, transformer impedences are a primary requirement.
  • The equivalent impedence of a transformer is not equal for two different voltage levels. Thus, for a power system network with two or more voltage levels, computing the equivalent impedence with reference to a single voltage level and then analysing the system per requirement turns out to be a complex activity.
  • The percentage impedence of a transformer however remains equal at all the voltage levels. This makes the calculation and analysis task easier. This is why transformer impedences are always specified in percentage.
Your response is private
Was this worth your time?
This helps us sort answers on the page.
Absolutely not
Definitely yes

Where do I start?

I’m a huge financial nerd, and have spent an embarrassing amount of time talking to people about their money habits.

Here are the biggest mistakes people are making and how to fix them:

Not having a separate high interest savings account

Having a separate account allows you to see the results of all your hard work and keep your money separate so you're less tempted to spend it.

Plus with rates above 5.00%, the interest you can earn compared to most banks really adds up.

Here is a list of the top savings accounts available today. Deposit $5 before moving on because this is one of th

Where do I start?

I’m a huge financial nerd, and have spent an embarrassing amount of time talking to people about their money habits.

Here are the biggest mistakes people are making and how to fix them:

Not having a separate high interest savings account

Having a separate account allows you to see the results of all your hard work and keep your money separate so you're less tempted to spend it.

Plus with rates above 5.00%, the interest you can earn compared to most banks really adds up.

Here is a list of the top savings accounts available today. Deposit $5 before moving on because this is one of the biggest mistakes and easiest ones to fix.

Overpaying on car insurance

You’ve heard it a million times before, but the average American family still overspends by $417/year on car insurance.

If you’ve been with the same insurer for years, chances are you are one of them.

Pull up Coverage.com, a free site that will compare prices for you, answer the questions on the page, and it will show you how much you could be saving.

That’s it. You’ll likely be saving a bunch of money. Here’s a link to give it a try.

Consistently being in debt

If you’ve got $10K+ in debt (credit cards…medical bills…anything really) you could use a debt relief program and potentially reduce by over 20%.

Here’s how to see if you qualify:

Head over to this Debt Relief comparison website here, then simply answer the questions to see if you qualify.

It’s as simple as that. You’ll likely end up paying less than you owed before and you could be debt free in as little as 2 years.

Missing out on free money to invest

It’s no secret that millionaires love investing, but for the rest of us, it can seem out of reach.

Times have changed. There are a number of investing platforms that will give you a bonus to open an account and get started. All you have to do is open the account and invest at least $25, and you could get up to $1000 in bonus.

Pretty sweet deal right? Here is a link to some of the best options.

Having bad credit

A low credit score can come back to bite you in so many ways in the future.

From that next rental application to getting approved for any type of loan or credit card, if you have a bad history with credit, the good news is you can fix it.

Head over to BankRate.com and answer a few questions to see if you qualify. It only takes a few minutes and could save you from a major upset down the line.

How to get started

Hope this helps! Here are the links to get started:

Have a separate savings account
Stop overpaying for car insurance
Finally get out of debt
Start investing with a free bonus
Fix your credit

Profile photo for Quora User

Percentage impedance is a significant parameter of a transformer. Percentage impedance means -

  1. The voltage drop occurring in the secondary winding of a transformer when the transformer is loaded fully. In your case, there will be a voltage drop of 12.4% from no-load secondary winding terminal voltage when the transformer supplies 55MVA. In this case, the percentage impedance is specified along with winding temperature since the resistance of the winding increases with winding temperature. As the load current increases, transformer winding temperature also increases and hence its impedance and t

Percentage impedance is a significant parameter of a transformer. Percentage impedance means -

  1. The voltage drop occurring in the secondary winding of a transformer when the transformer is loaded fully. In your case, there will be a voltage drop of 12.4% from no-load secondary winding terminal voltage when the transformer supplies 55MVA. In this case, the percentage impedance is specified along with winding temperature since the resistance of the winding increases with winding temperature. As the load current increases, transformer winding temperature also increases and hence its impedance and thus the voltage drop.
  2. The percentage of primary voltage when applied to the primary winding of the transformer will result in full load secondary winding current with the secondary winding terminals short-circuited.
  3. The short circuit capacity of the transformer. The percentage impedance specifies the maximum short circuit current that can be fed by the transformer when its secondary winding is short circuited and rated voltage is applied to its primary winding. In this case, the percentage impedance is used to determine the available short circuit capacity or the fault level at the point in the electrical system where the transformer secondary is connected. Percentage impedance is also used to calculate the voltage drop that will occur in the system when a large motor connected to the system to which the transformer feeds power is started.
Profile photo for Quora User

"The percentage impedance of a transformer is the voltage drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage."

"It is also the percentage of the normal terminal voltage at one side required to circulate full-load current under short circuit conditions on other side."

The impedance of a transformer has a major effect on system fault levels. It determines the maximum value of current that will flow under fault conditions.

It is easy to calculate the maximum current that a transformer can deliver under symmetrical fault co

"The percentage impedance of a transformer is the voltage drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage."

"It is also the percentage of the normal terminal voltage at one side required to circulate full-load current under short circuit conditions on other side."

The impedance of a transformer has a major effect on system fault levels. It determines the maximum value of current that will flow under fault conditions.

It is easy to calculate the maximum current that a transformer can deliver under symmetrical fault conditions. By way of example, consider a 2 MVA transformer with an impedance of 5%. The maximum fault level available on the secondary side is:

2 MVA x 100/5 = 40 MVA

and from this figure, the equivalent primary and secondary fault currents can be calculated.

A transformer with a lower impedance will lead to a higher fault level (and vice versa).

The figure calculated above is a maximum. In practice, the actual fault level will be reduced by the source impedance, the impedance of cables and overhead lines between the transformer and the fault, and the fault impedance itself.

Profile photo for Quora User

Here’s the thing: I wish I had known these money secrets sooner. They’ve helped so many people save hundreds, secure their family’s future, and grow their bank accounts—myself included.

And honestly? Putting them to use was way easier than I expected. I bet you can knock out at least three or four of these right now—yes, even from your phone.

Don’t wait like I did. Go ahead and start using these money secrets today!

1. Cancel Your Car Insurance

You might not even realize it, but your car insurance company is probably overcharging you. In fact, they’re kind of counting on you not noticing. Luckily,

Here’s the thing: I wish I had known these money secrets sooner. They’ve helped so many people save hundreds, secure their family’s future, and grow their bank accounts—myself included.

And honestly? Putting them to use was way easier than I expected. I bet you can knock out at least three or four of these right now—yes, even from your phone.

Don’t wait like I did. Go ahead and start using these money secrets today!

1. Cancel Your Car Insurance

You might not even realize it, but your car insurance company is probably overcharging you. In fact, they’re kind of counting on you not noticing. Luckily, this problem is easy to fix.

Don’t waste your time browsing insurance sites for a better deal. A company called Insurify shows you all your options at once — people who do this save up to $996 per year.

If you tell them a bit about yourself and your vehicle, they’ll send you personalized quotes so you can compare them and find the best one for you.

Tired of overpaying for car insurance? It takes just five minutes to compare your options with Insurify and see how much you could save on car insurance.

2. Ask This Company to Get a Big Chunk of Your Debt Forgiven

A company called National Debt Relief could convince your lenders to simply get rid of a big chunk of what you owe. No bankruptcy, no loans — you don’t even need to have good credit.

If you owe at least $10,000 in unsecured debt (credit card debt, personal loans, medical bills, etc.), National Debt Relief’s experts will build you a monthly payment plan. As your payments add up, they negotiate with your creditors to reduce the amount you owe. You then pay off the rest in a lump sum.

On average, you could become debt-free within 24 to 48 months. It takes less than a minute to sign up and see how much debt you could get rid of.

3. You Can Become a Real Estate Investor for as Little as $10

Take a look at some of the world’s wealthiest people. What do they have in common? Many invest in large private real estate deals. And here’s the thing: There’s no reason you can’t, too — for as little as $10.

An investment called the Fundrise Flagship Fund lets you get started in the world of real estate by giving you access to a low-cost, diversified portfolio of private real estate. The best part? You don’t have to be the landlord. The Flagship Fund does all the heavy lifting.

With an initial investment as low as $10, your money will be invested in the Fund, which already owns more than $1 billion worth of real estate around the country, from apartment complexes to the thriving housing rental market to larger last-mile e-commerce logistics centers.

Want to invest more? Many investors choose to invest $1,000 or more. This is a Fund that can fit any type of investor’s needs. Once invested, you can track your performance from your phone and watch as properties are acquired, improved, and operated. As properties generate cash flow, you could earn money through quarterly dividend payments. And over time, you could earn money off the potential appreciation of the properties.

So if you want to get started in the world of real-estate investing, it takes just a few minutes to sign up and create an account with the Fundrise Flagship Fund.

This is a paid advertisement. Carefully consider the investment objectives, risks, charges and expenses of the Fundrise Real Estate Fund before investing. This and other information can be found in the Fund’s prospectus. Read them carefully before investing.

4. Earn Up to $50 this Month By Answering Survey Questions About the News — It’s Anonymous

The news is a heated subject these days. It’s hard not to have an opinion on it.

Good news: A website called YouGov will pay you up to $50 or more this month just to answer survey questions about politics, the economy, and other hot news topics.

Plus, it’s totally anonymous, so no one will judge you for that hot take.

When you take a quick survey (some are less than three minutes), you’ll earn points you can exchange for up to $50 in cash or gift cards to places like Walmart and Amazon. Plus, Penny Hoarder readers will get an extra 500 points for registering and another 1,000 points after completing their first survey.

It takes just a few minutes to sign up and take your first survey, and you’ll receive your points immediately.

5. Get Up to $300 Just for Setting Up Direct Deposit With This Account

If you bank at a traditional brick-and-mortar bank, your money probably isn’t growing much (c’mon, 0.40% is basically nothing).

But there’s good news: With SoFi Checking and Savings (member FDIC), you stand to gain up to a hefty 3.80% APY on savings when you set up a direct deposit or have $5,000 or more in Qualifying Deposits and 0.50% APY on checking balances — savings APY is 10 times more than the national average.

Right now, a direct deposit of at least $1K not only sets you up for higher returns but also brings you closer to earning up to a $300 welcome bonus (terms apply).

You can easily deposit checks via your phone’s camera, transfer funds, and get customer service via chat or phone call. There are no account fees, no monthly fees and no overdraft fees. And your money is FDIC insured (up to $3M of additional FDIC insurance through the SoFi Insured Deposit Program).

It’s quick and easy to open an account with SoFi Checking and Savings (member FDIC) and watch your money grow faster than ever.

Read Disclaimer

5. Stop Paying Your Credit Card Company

If you have credit card debt, you know. The anxiety, the interest rates, the fear you’re never going to escape… but a website called AmONE wants to help.

If you owe your credit card companies $100,000 or less, AmONE will match you with a low-interest loan you can use to pay off every single one of your balances.

The benefit? You’ll be left with one bill to pay each month. And because personal loans have lower interest rates (AmONE rates start at 6.40% APR), you’ll get out of debt that much faster.

It takes less than a minute and just 10 questions to see what loans you qualify for.

6. Lock In Affordable Term Life Insurance in Minutes.

Let’s be honest—life insurance probably isn’t on your list of fun things to research. But locking in a policy now could mean huge peace of mind for your family down the road. And getting covered is actually a lot easier than you might think.

With Best Money’s term life insurance marketplace, you can compare top-rated policies in minutes and find coverage that works for you. No long phone calls. No confusing paperwork. Just straightforward quotes, starting at just $7 a month, from trusted providers so you can make an informed decision.

The best part? You’re in control. Answer a few quick questions, see your options, get coverage up to $3 million, and choose the coverage that fits your life and budget—on your terms.

You already protect your car, your home, even your phone. Why not make sure your family’s financial future is covered, too? Compare term life insurance rates with Best Money today and find a policy that fits.

Profile photo for Quora User

I believe transformer impedance is given in percentage term as it reflects to how good or well a transformer was designed for power conversion.. It is the portion of the transformer’s efficiency that is lost or used-up during the process of power conversion..

Based on a 100% power conversion efficiency for a perfectly designed unit. A 10 % impedance will indicate that the unit will only be only 90% efficient.. Since 10% of the power is lost, represented in terms of voltage drop as the transformer gets fully loaded… Voltage drops due to winding resistance and leakage reactances of the transforme

I believe transformer impedance is given in percentage term as it reflects to how good or well a transformer was designed for power conversion.. It is the portion of the transformer’s efficiency that is lost or used-up during the process of power conversion..

Based on a 100% power conversion efficiency for a perfectly designed unit. A 10 % impedance will indicate that the unit will only be only 90% efficient.. Since 10% of the power is lost, represented in terms of voltage drop as the transformer gets fully loaded… Voltage drops due to winding resistance and leakage reactances of the transformer..

Profile photo for Aravind S Kumar

The normal impedance of a transformer can be specified either with respect to primary or with respect to secondary.
When the impedance is specified in ohms it becomes necessary to specify referred to which side and we'll have to calculate if we want it with respect to the other side.
If the transformer impedance is given by per unit(or percentage) it remains same when referred to both sides and hence calculation becomes easier.

%impedance = actual impedance/ base impedance *100
base impedance = square of rated voltage/rated power
Zbase = KVrating^2/MVArating

Am I the only one who never knew this before?
Profile photo for Sherlin Smith

The impedance of a transformer is defined as the percentage of the drop in voltage to the at full load to the rated voltage of the transformer. This drop in voltage is due to the winding resistance and leakage reactance.

Alternatively, the percentage of a transformer can be described as the percentage of the nominal voltage in the primary that is required to circulate the rated current in the secondary.

The impedance of a transformer can be measured by means of a short-circuit test.

The secondary of the transformer whose percentage impedance is to be measured is shorted. The voltage on the prim

The impedance of a transformer is defined as the percentage of the drop in voltage to the at full load to the rated voltage of the transformer. This drop in voltage is due to the winding resistance and leakage reactance.

Alternatively, the percentage of a transformer can be described as the percentage of the nominal voltage in the primary that is required to circulate the rated current in the secondary.

The impedance of a transformer can be measured by means of a short-circuit test.

The secondary of the transformer whose percentage impedance is to be measured is shorted. The voltage on the primary is gradually increased from zero till the secondary current reaches the transformer's rated value.

The percentage impedance of the transformer is calculated as

Z%= (Impedance Voltage/Rated Voltage)*100

Thus a transformer with a primary rating of 110V which requires a voltage of 10V to circulate the rated current in the short-circuited secondary would have an impedance of 9%.

The percentage impedance of a transformer a crucial parameter when operating transformers in parallel. It also determines the fault level of a system during faults

Profile photo for Suryanarayana Danturti

% Impedance is a very important parameter of a transformer.For distribution transformers it is generally between 4% to 6% and for power transformers is in the range of 6% to 8%.

If the %impedance is more,there is more voltage drop in the transformer that means for distribution transformers from where the consumers are connected,lesser voltage drop is preferred and hence select a transformer with lesser value of % impedance.

The % impedance is useful in calculating the short circuit current on the secondary side of the transformer and is given by

Short circuit current in KVA = Transformer rating K

% Impedance is a very important parameter of a transformer.For distribution transformers it is generally between 4% to 6% and for power transformers is in the range of 6% to 8%.

If the %impedance is more,there is more voltage drop in the transformer that means for distribution transformers from where the consumers are connected,lesser voltage drop is preferred and hence select a transformer with lesser value of % impedance.

The % impedance is useful in calculating the short circuit current on the secondary side of the transformer and is given by

Short circuit current in KVA = Transformer rating KVA/per unit impedance

For example if the rating of transformer is 500 KVA and %impedance is 5% or 0.05 p.u.

Short circuit rating in KVA = 500/0.05 =10,000 KVA or 10 MVA

Knowing the short circuit current is important to select circuit breaker breaking capacity,rating of bus bars,relay settings etc and for calculation of cable sizes.

Profile photo for Tyler G. Minix

It allows for more simple calculations. When everything (voltage, current. power, impedance, etc.) is given p.u. (per unit, or, percentage) we don’t have to mind our units. It just makes fore easier calculation. It’s the industry standard measurement method for power systems so that’s why transformer manufacturers print impedance in p.u. (percentage).

Profile photo for Lipsamayi Dash

The impedance of a transformer is defined as the percentage of the drop in voltage to the at full load to the rated voltage of the transformer. This drop in voltage is due to the winding resistance and leakage reactance.

The percentage impedance of the transformer is calculated as

Z%= (Impedance Voltage/Rated Voltage)*100

ex:A transformer with a primary rating of 110V which requires a voltage of 10V to circulate the rated current in the short-circuited secondary would have an impedance of 9%.

Profile photo for Quora User

Because it is easy to convert them back to P.U. (Per Unit) system which makes calculations a lot easier, especially, in the case of impedance calculation referring to the primary or secondary side of the transformer, or in the case of 3 phase calculation, such as fault analysis in power system.

Profile photo for Tino Wymann

Because the transformer also transforms the impedance and it is different whether you look at it from primary or secondary side. And also it's more handy to have it relative to the nominal rating of the transformer. The reference impedance is by the way:

[math]\frac{V^2}{S} [/math]

Profile photo for Vaibhav Mani

Transformer’s impedance is given in percentage or per unit system . It is because of the reason that impedance value for transformer is reperesented as two values one wrt to low voltage winding and other wrt high voltage winding . Both values are different but represent the very same physical quantity . Thats why it becomes sometimes ambiguous for engineers to use thee values correctly . To cope with this problem , per unit system is used . In p.u. system representation , for both HV winding as well as LV winding , impedance value will be same .

1. Per unit impedance remain same on both primary and secondary side of transformer. It simplify calculations, especially power system where we have number of transformers.
2. If you see the per unit impedance of transformers of any rating you will find that they all lie ( on their respective base) in a narrow range.

Profile photo for Dmitry Tor

The percentage impedance of a transformer is the volt drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage.

It is also the percentage of the normal terminal voltage required to circulate full-load current under short circuit conditions.

Profile photo for Srinath Visweswaran

The percentage (per unit representation) is used so that you can calculate impedance based on the transformer ratings. The impedance (in ohms) is different with variation in voltage but if you know the per unit value then even with variations in voltage you can find out the impedance. This is particularly useful when conducting fault analysis.

Profile photo for Shib Maitra

Transformer has primary winding impedance and secondary winding impedance. Percentage or per unit impedance expresses percentage equivalent impedance. A 4% percent or .04 per unit impedance will mean it will cause at fulll load a voltage drop of 4% of secondary voltage.

Profile photo for Mohamed Rafeequdin

Please refer to my answer for almost similar question.

Why is the transformer impedance given in percentage?

Profile photo for Alejandro Nava

Short answer: Each winding of a transformer has a resistance and a self-inductance. So in the phasor domain, each winding has a complex impedance. The combination of the complex impedances of the two windings, where one impedance must be referred to the other side, is known as the equivalent impedance of the transformer, and depends on the side of the transformer it is referred to. This equivalent impedance can be expressed as a per-unit of the base impedance of the transformer, and the result is also a complex number known as the per-unit equivalent impedance of the transformer, and is indepe

Short answer: Each winding of a transformer has a resistance and a self-inductance. So in the phasor domain, each winding has a complex impedance. The combination of the complex impedances of the two windings, where one impedance must be referred to the other side, is known as the equivalent impedance of the transformer, and depends on the side of the transformer it is referred to. This equivalent impedance can be expressed as a per-unit of the base impedance of the transformer, and the result is also a complex number known as the per-unit equivalent impedance of the transformer, and is independent of the side of the transformer it is referred to. The magnitude of the per-unit equivalent impedance of the transformer, expressed as percentage (i.e. multiplied by 100), is known as the percentage impedance of the transformer.

Long answer: To understand the above paragraph, you need to know 1) the equivalent circuit model of a single-phase two-winding transformer, including the meaning of each element of such model; and 2) the per-unit system. Below I’ll do a review of those concepts. Then I’ll illustrate with an example.


1. The equivalent circuit of a transformer

Below I show the equivalent circuit of a practical single-phase two-winding transformer operating at low frequencies in sinusoidal steady-state. Let’s decompose the previous phrase so that we understand the limitations of the following equivalent circuit:

  • The word equivalent means it is a mathematical model [with errors] of a physical system.
  • The phrase single-phase means it has only one set of windings, whose voltages are either in phase or phase-shifted by 180° (depending on the reference polarity of the voltages and the relative orientation of the windings i.e. the dots).
  • The phrase two-winding means it has two windings for each set of windings.
  • As a side note, there are three-phase two-winding transformers, and three-phase three-winding transformers.
  • The phrase at low frequencies means at 50 Hz or 60 Hz (the model of a radio-frequency transformer is different, for example it includes capacitance between both windings).
  • The phrase in sinusoidal steady state means the voltages and currents waveforms are sinusoidal (the model of a transformer for harmonics analysis is different, and the model is also different during transient state i.e. during inrush current when the transformer is first connected to the power grid).

Figure 1. Equivalent circuit, complete, exact, in real values, without eliminating the ideal transformer. Source: [1].

First, let’s quickly remember each of the elements of the above model:

  • The resistances [math]R_p[/math] and [math]R_s[/math] represent the AC resistance or apparent resistance of the conductors of the windings; it is higher than the DC resistance or effective resistance due to the skin effect and proximity effect.
  • The inductive reactances [math]X_p[/math] and [math]X_s[/math] represent the self-inductance of each winding, which is due to the magnetic field by the current in that winding that doesn’t link to the other winding.
  • The shunt branch or parallel branch has two purposes, the first being to account for the fact that in a practical transformer, one side draws current (when it is energized/connected to a voltage source) even when the other side is open-circuited, which doesn’t happen in an ideal transformer; the second purpose of the shunt branch is to account for [math]R_N[/math] and [math]X_M[/math].
    • The resistance [math]R_N[/math] represents the iron core losses, that is, losses due to eddy currents and due to hysteresis in the ferromagnetic core.
    • The inductive reactance [math]X_M[/math] represents the magnetizing current, which has harmonics but its fundamental components lags the applied voltage by 90°.
    • Keep in mind the hysteresis of a ferromagnetic core is a non-linear phenomena; that is, the hysteresis loop relating the exciting current and the flux is non-linear. Moreover, it isn’t even a single-valued function; that is, for a given value of the exciting current, the flux can have two values, one when it is rising and another when it is decreasing. Furthermore, the shape of the hysteresis loop depends on the peak value of the exciting current and the flux, meaning we can’t determine on which hysteresis loop from a family of hysteresis loops the core is operating until we know the peak value of either the exciting current or the flux. All of these difficulties are neglected when modeling this phenomena as a constant resistance [math]R_N[/math].
    • Also keep in mind the magnetizing current is non-sinusoidal even if the applied voltage is sinusoidal. So it has harmonics. But they are neglected when modeling this phenomena as a constant inductive reactance [math]X_M[/math].
    • The reason why [math]R_N[/math] and [math]X_M[/math] are placed in parallel in the model is because the magnetizing current (in the non-saturated region of the core) and the core losses current are proportional to the applied voltage.

2. Simplified equivalent circuits of a transformer

Secondly, let’s remember how we manipulate the above equivalent circuit to obtain others.

We can simplify this circuit by referring one side to the other. For that, remember that if the turns ratio [math]a[/math] is defined as [math]N_p/N_s[/math], then to eliminate the transformer and refer the secondary side into the primary side, we use:

[math]Z_s’ = a^2 Z_s; {\mathbf V}_s’ = a {\mathbf V}_s; {\mathbf I}_s’ = \dfrac{{\mathbf I}_s}{a} \tag*{}[/math]

while to eliminate the transformer and refer the primary side into the secondary side, we use:

[math]Z_p’ = \dfrac{Z_p}{a^2}; {\mathbf V}_p’ = \dfrac{{\mathbf V}_p}{a}; {\mathbf I}_p’ = a {\mathbf I}_s \tag*{}[/math]

where

[math]Z_s = R_s + j X_s; Z_p = R_p + j X_p \tag*{}[/math]

With the above two rules, we can refer the impedances, voltages and currents from one side to the other in the circuit of figure 1:

Figure 2. Equivalent circuit, complete, exact, in real values, with ideal transformer eliminated and referred to the primary side. Source: [1].

Figure 3. Equivalent circuit, complete, exact, in real values, with ideal transformer eliminated and referred to the secondary side. Source: [1].

Under full-load, the primary and secondary currents of a transformer are much greater than the exciting current. So, we can move the shunt branch to the left (before the series impedance of the primary), which results in an approximated circuit as shown below, but whose results are very close to the exact model of figures 1, 2 and 3. After moving the shunt branch, we can combine the series impedances of both windings into one (or we can just combine the series resistances into one and the series reactances into one, without combining the equivalent resistance and equivalent reactance into one):

Figure 4. Equivalent circuit, complete, approximated (with excitation branch moved), in real values, with ideal transformer eliminated and referred to the primary side. Source: [1].

Figure 5. Equivalent circuit, complete, approximated (with excitation branch moved), in real values, with ideal transformer eliminated and referred to the secondary side. Source: [1].

As mentioned earlier, the exciting current is very small (less than about 5%) of the total current. In power systems analysis, the excitation branch is neglected altogether, so the complete exact circuit of figures 2 and 3 (and the complete approximated circuit of figures 4 and 5) becomes:

Figure 6. Equivalent circuit, incomplete (with excitation branch neglected) and thus approximated, in real values, with ideal transformer eliminated and referred to the primary side. Source: [1].

Figure 7. Equivalent circuit, incomplete (with excitation branch neglected) and thus approximated, in real values, with ideal transformer eliminated and referred to the secondary side. Source: [1].

In the previous figure, the equivalent series resistance can be combined with the equivalent series reactance:

[math]\begin{align} Z_{\text{eq } p} &= R_{\text{eq } p} + j X_{\text{eq } p} \\ &= (R_p + a^2 R_s) + j(X_p + a^2 X_s) \end{align} \tag*{}[/math]

[math]\begin{align} Z_{\text{eq } s} &= R_{\text{eq } s} + j X_{\text{eq } s} \\ &= \left(\dfrac{R_p}{a^2} + R_s \right) + j \left(\dfrac{X_p}{a^2} + X_s \right) \end{align} \tag*{}[/math]

In certain power systems studies, for large transformers, even the equivalent series resistance is neglected (because it is small compared to the equivalent series reactance), and the transformer is represented by a mere equivalent series reactance. But I won’t consider this to be the case, since that’s a particular case.

The takeaway of the above discussion is the equivalent circuit of figures 4 and 5, and the meaning of [math]Z_{\text{eq } p}[/math] and [math]Z_{\text{eq } s}[/math]:

  • [math]Z_{\text{eq } p}[/math] is the series impedance of the primary winding combined with the series impedance of the secondary winding referred to the primary winding, expressed in real values (ohms).
  • [math]Z_{\text{eq } s}[/math] is the series impedance of the primary winding referred to the secondary winding combined with the series impedance of the secondary winding, expressed in real values (ohms).

3. The per-unit measuring system for single-phase transformers

Third and lastly, let’s remember the per-unit system. The per-unit value of a quantity (current [phasor or just magnitude], voltage [phasor or just magnitude], active power, reactive power, apparent power, complex power, impedance [complex or just magnitude], admittance [complex or just magnitude]) is the real value (in amperes, volts, watts, volt-amperes, volt-amperes reactive, ohms or siemens) of the quantity expressed as a fraction of another value (with the same units). That another value is known as the base value. The result is a dimensionless number.

Notice the per-unit value corresponding to a real value depends on the value chosen as base. Any arbitrary number can be chosen as base value, but once a base value has been chosen for two electric quantities, the base value of the rest of the electric quantities is determined by the circuit equations.

In transformers, the base values for the primary and secondary voltages are chosen, and for the apparent power. These are not arbitrarily chosen as explained above, but instead are chosen to be the same as the rated primary and rated secondary voltages and the rated apparent power. The reason is that by choosing the base primary voltage and base secondary voltage such that their ratio is the same as the ratio of the rated primary voltage and rated secondary voltage, it can be mathematically shown the turns ratio in the equivalent per-unit circuit, [math]a'[/math], is equal to 1, which means the circuits of figures 4 and 5 are simplified and become the following:

Figure 8. Equivalent circuit, complete, approximated (with excitation branch moved), in per-unit values, with ideal transformer eliminated and referred to the primary side. Source: [1], edited.

Figure 9. Equivalent circuit, complete, approximated (with excitation branch moved), in per-unit values, with ideal transformer eliminated and referred to the secondary side. Source: [1], edited.

After that, the base values for the per-unit currents and per-unit impedances are calculated using the base values for the per-unit voltages and per-unit apparent power and using the circuit equations. And after that, the equivalent series impedance of the transformer is converted from a real value to a per-unit value by dividing it by the computed base impedance.


Example: Consider a single-phase two-winding power transformer whose ratings are 20 kVA, 8 000 V/240 V. After performing the short-circuit test and open-circuit test, it is found the equivalent series impedance referred to the primary side (high-voltage side) is [math]Z_{\text{eq } p} = (38.4 + j 192) \, \Omega[/math] (that is, [math]R_{\text{eq } p} = 38.4 \, \Omega[/math] and [math]X_{\text{eq } p} = 192 \, \Omega[/math]). Determine the series impedance in per-unit, and the percentage impedance and [math]X/R[/math] ratio of the transformer.

Solution: The base value for the primary and secondary voltages are chosen to be the same as the rated voltages, that is:

[math]V_\text{b,p} = 8 \, 000 \text{ V} \tag*{}[/math]

[math]V_\text{b,s} = 240 \text{ V} \tag*{}[/math]

The base value for the apparent power is chosen to be the same as the rated power, that is:

[math]S_\text{b} = 20 \, 000 \text{ VA} \tag*{}[/math]

Now we use the circuit equations to obtain the base value of the other electrical quantities. For the base value of the impedance in the primary side:

[math]\begin{align} S &= \dfrac{V^2}{Z} \\ \implies S_\text{b} &= \dfrac{V_\text{b,p}^2}{Z_\text{b,p}} \\ \implies Z_\text{b,p} &= \dfrac{V_\text{b,p}^2}{S_\text{b}} \\ &= \dfrac{(8 \, 000 \text{ V})^2}{(20 \, 000 \text{ VA})} = 3 \, 200 \, \Omega \end{align} \tag*{}[/math]

and for the base value of the impedance in the secondary side:

[math]\begin{align} Z_\text{b,s} &= \dfrac{V_\text{b,s}^2}{S_\text{b}} \\ &= \dfrac{(240 \text{ V})^2}{(20 \, 000 \text{ VA})} = 2.88 \, \Omega \end{align} \tag*{}[/math]

Now that we’ve determined the base values, we can compute the per-unit values by dividing the real values by the base values. In this example, it is stated the given equivalent series impedance is referred to the primary side, so we must use the base value of the impedance in the primary side to find the per-unit value of the equivalent series impedance:

[math]\begin{align} Z_{\text{eq } p \text{,pu}} &= \dfrac{Z_{\text{eq } p}}{Z_\text{b,p}} \\ &= \dfrac{(38.4 + j 192) \, \Omega}{3 \, 200 \, \Omega} = (0.012 + j0.06) \text{ pu} \end{align} \tag*{}[/math]

So, 0.012 + j0.06 is the per-unit equivalent series impedance of the transformer referred to the primary side.

And what about the per-unit series impedance referred to the secondary side? For that, we must first refer the given series impedance to the secondary side:

[math]\begin{align} Z_{\text{eq } s} &= \dfrac{Z_{\text{eq } p}}{a^2} \\ &= \dfrac{(38.4 + j 192) \, \Omega}{ \left( \dfrac{8 \, 000 \text{ V}}{240 \text{ V}} \right)^2} = (0.03456 + j0.1728) \, \Omega \end{align} \tag*{}[/math]

thus, the per-unit equivalent series impedance of the transformer referred to the secondary side is:

[math]\begin{align} Z_{\text{eq } s \text{,pu}} &= \dfrac{Z_{\text{eq } s}}{Z_\text{b,s}} \\ &= \dfrac{(0.03456 + j0.1728) \, \Omega}{2.88 \, \Omega} = (0.012 + j0.06) \text{ pu} \end{align} \tag*{}[/math]

which is the same as the per-unit equivalent series impedance of the transformer referred to the primary side. This shows the per-unit equivalent series impedance of a transformer is the same irrespective of the side. So, when specifying the equivalent series impedance of a transformer in per-unit, it’s not necessary to state if it is referred to the high-voltage or low-voltage side, or the primary or secondary side. So we can drop the subscript “p” and “s” in the per-unit equivalent series impedance.

For the given transformer, it is possible to find the percentage impedance and the [math]X/R[/math] ratio. For the percentage impedance, first we express the per-unit impedance ([0.012 + j 0.06] pu) in polar form:

[math]\begin{align} Z_{\text{eq} \text{,pu}} &= \sqrt{0.012^2 + 0.06^2} \, \angle \tan^{-1}{(0.06/0.012)} \text{ pu} \\ &\approx 0.0612 \angle 78.69^\circ \text{ pu} \end{align} \tag*{}[/math]

Now we multiply the magnitude of the per-unit impedance by 100 to express it as a percentage. The result will be the percentage impedance of the transformer:

[math]\%|Z_\text{eq}| = |Z_{\text{eq} \text{,pu}}| \cdot 100 = 0.0612 \text{ pu} \cdot 100 = 6.12\% \tag*{}[/math]

The [math]X/R[/math] ratio of the transformer is:

[math]\dfrac{X_{\text{eq} \text{,pu}}}{R_{\text{eq} \text{,pu}}} = \dfrac{0.06\text{ pu}}{0.012\text{ pu}} = 5 \tag*{}[/math]


4. References

[1] Chapman, Stephen. Electric Machinery Fundamentals (4th edition). Chapter 2.

[2] Massachusetts Institute of Technology. Magnetic Circuits and Transformers: a first course for power and communication engineers. Chapter VI.

[3] Alexander, Charles K.; O. Sadiku, Matthew N. Fundamentals of Electric Circuits (5th edition). Chapter 13.

[4] Kothari, D. P.; Nagrath, I. J. Electric Machines (4th edition). Chapter 3.

Profile photo for Saicharan.

Various equipments used in power system have different KVA ratings. Therefore,it is necessary to find percentage reactances of all elements on a common KVA ratng

Profile photo for Steven Wilson

The percentage impedance of a transformer reflects the voltage drop (at full load) due to the winding resistance and leakage reactance, expressed as a percentage of the rated voltage. It is also the percentage of the normal terminal voltage that is required to circulate full-load current under short circuit conditions. It is indeed dependent on the design of the transformer core including the size and cross-sectional area of the coil/winding(s).

Profile photo for Kev Go

You will likely need a suitable variable AC supply like an variac (variable AC power supply) as shown below to do this without damaging the transformer. Also a high current AC ammeter or tong tester with suitable capacity to measure the full load secondary current.

Place a short across the secondary. Connect the primary to the variac and SLOWLY wind the primary voltage up to where the secondary cur

You will likely need a suitable variable AC supply like an variac (variable AC power supply) as shown below to do this without damaging the transformer. Also a high current AC ammeter or tong tester with suitable capacity to measure the full load secondary current.

Place a short across the secondary. Connect the primary to the variac and SLOWLY wind the primary voltage up to where the secondary current = the full load current in the secondary.

VA (VoltAmps)/ secondary Volts = the full load current. Record the secondary current and the primary voltage with a full load current is flowing in the ...

Profile photo for Arnold Goldman

I fully agree with the answers already offered

Profile photo for Curt Weinstein

Impedance (of an alternating current) is almost like resistance in a direct current. A difference is with resistance, the energy is gone into heat. With impedance, the energy is stored (or lost) in space. Bigger coils tend to have more impedance.

Profile photo for Muralidhar Rao

Impedance at 75 degree Celsius 12.4% @ 55MVA ; it means that a power transformer on full load condition during transmission the temp. of that transformer rises to 75 degrees Celsius, the max impedance would be only 12.4% which is healthy state of that transformer as Manufacturer's claim(resistance of coil + inductance of transformer does matter for rise in temp.)

Profile photo for Ahindrila Das

The percentage impedance value which is a measure of full load is given for an MVA of 55 at 75 degree celsius. use this link to help you calculate that better

Calculating the percentage impedance of a Transformer

Profile photo for Pankaj Gupta

In power system,analysis is done in per unit basis,as X-mer shows percentage amount of per-unit impedance of it.

Profile photo for Abhishek Jangid

The percentage impedance of a transformer is the volt drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage.

It is also the percentage of the normal terminal voltage required to circulate full-load current under short circuit conditions

Profile photo for Anonymous
Anonymous

We use per unit system for calculation purpose in Power System. Presence of transformer causes discontinuity in power system. In order to overcome / avoid we use per unit method that's why all values are in per unit and hence impedances also written in their % or per Unit system.

Profile photo for Dr. Arpan Hota

Often transformers are used for parallel operation. To share the load equally transformers must have to have equal percentage impedance. If it would be given in absolute value again we have to calculate the percentage value then use it. to save the trouble you get it in percentage.

Profile photo for Vishal Bhosale

1.Firstly, impedance is the combination of resistance and leakage reactance.

2.Percentage impedance of a transformer is nothing but the voltage drop occurred in transformer at full load loading.

3.Now, this impedance drop(voltage drop) is expressed in terms of percentage of terminal voltage. Therefore the transformer impedance drop is given in percentage.

Profile photo for Shrikant Shanker

We have Short circuit test to calculate the impedance of the transformer.

For this, low voltage side of the transformer is short circuited, an auto transformer and voltmeter is connected to higher voltage side.

An ammeter is connected to the lower voltage side(short circuited side).

Initially the auto transformer is gives ZERO voltage.

Now voltage is increased gradually.

The ammeter in the secondary side ( Low voltage side in our case) will will sense some current. Now voltage is increased by adjusting the auto transformer till the ammeter on other side shows the normal full load current.

Now th

We have Short circuit test to calculate the impedance of the transformer.

For this, low voltage side of the transformer is short circuited, an auto transformer and voltmeter is connected to higher voltage side.

An ammeter is connected to the lower voltage side(short circuited side).

Initially the auto transformer is gives ZERO voltage.

Now voltage is increased gradually.

The ammeter in the secondary side ( Low voltage side in our case) will will sense some current. Now voltage is increased by adjusting the auto transformer till the ammeter on other side shows the normal full load current.

Now this is the point where we can calculate the impedance.

Lets have an example.-

Transformer rating 10 KVA

Single phase primary voltage- 480 V.

Secondary voltage - 240 V

Full load current - (10 kVA X 1000)/(240 V)

- 41.67 A

Now the experiment- Assume the primary voltage injected is 24 V at which the ammeter reads 41.7 A (Transformer full load current).

Impedance is ratio of 24 V to 480 V,

i.e. Impedance Z = 24/480 =0.05.

But the impedance of transformer is expressed in %, So the

% impedance is 0.05 X 100 =5%.

Hope it helps.

Your response is private
Was this worth your time?
This helps us sort answers on the page.
Absolutely not
Definitely yes
Profile photo for Jim P

In general, it increases but it depends.

A transformer’s impedance as given on the nameplate is actually a measure of the magnitude of the winding resistance in series with the inductive reactance caused by the leakage flux. There are also core loss and magnetizing components but I’m skipping a discussion of those for the purpose of this answer.

An ideal transformer has perfect magnetic coupling between all windings with no leakage flux. The impedance would, therefore, only be the winding resistance.

For a non-ideal transformer, the magnetic coupling is not perfect due to leakage flux and this ca

In general, it increases but it depends.

A transformer’s impedance as given on the nameplate is actually a measure of the magnitude of the winding resistance in series with the inductive reactance caused by the leakage flux. There are also core loss and magnetizing components but I’m skipping a discussion of those for the purpose of this answer.

An ideal transformer has perfect magnetic coupling between all windings with no leakage flux. The impedance would, therefore, only be the winding resistance.

For a non-ideal transformer, the magnetic coupling is not perfect due to leakage flux and this causes the magnitude of the impedance to be greater. How much greater depends on many factors like the type of core, how the windings are arranged, the geometry of the coils, the shape of the wire, the amount and type of insulation used, and other factors.

For large power transformers that operate at high voltages, the impedance tends to increase with the physical size of the coils. For example, small distribution transformer banks like this

will typically have a small impedance of about 2%.

For large substation transformers that operate at high voltage levels,

the impedance will be much greater, typically over 9%, and will increase as the geometry and size of the coils increase.


In the power industry, the percent-impedance as stamped on the transformer nameplate is actually known as the impedance-voltage and is defined to be the voltage necessary to cause rated current to flow in the high-voltage winding when a short-circuit is placed on the low-voltage winding.

For example, given a full-load apparent power rating of 100 MVA and 138 kV line-to-line, the full load current will be 418 A in the high-voltage winding. If, during the short-circuit test, a voltage of 13.8 kV was required to achieve 418 A, the impedance-voltage would be 10%. Given the base impedance of 190 ohms as calculated from the nameplate ratings above, the transformer impedance would be 19 ohms (i.e., 10% of the base). This impedance is a single-phase equivalent. It is equal to the magnitude of the equivalent resistance in series with the inductive reactance of the leakage flux of both the primary and secondary windings. This is typically given by an x/r ratio. For small transformers, the x/r ratio is very low like 0.9 or less. For large transformers, the x/r ratio is high like 10 or more. So, for the large substation transformers, the leakage reactance is approximately equal to the impedance magnitude.

Footnotes

Profile photo for Ralph Gould

The number of turns of wire in the coil directly affect the values of resistance and inductance. Those 2 values largely determine the impedance across a frequency band. Capacitance in the winding plus a role as well.

Profile photo for RP Deshpande

Impedance of transformer, expressed as the percentage of rated impedance of load at full rated current, is called percentage impedance. This is a very useful quantity for transformer calculations.

This impedance is calculated from short circuit test data, when a small primary voltage produces full load current in secondary of transformer. This small voltage on primary side, expressed as percentage of full rated voltage , is called percentage impedance.

This is useful quantity from which short circuit KVA or MVA can be easily calculated. In case of fault, maximum MVA that can flow in the cable is

Impedance of transformer, expressed as the percentage of rated impedance of load at full rated current, is called percentage impedance. This is a very useful quantity for transformer calculations.

This impedance is calculated from short circuit test data, when a small primary voltage produces full load current in secondary of transformer. This small voltage on primary side, expressed as percentage of full rated voltage , is called percentage impedance.

This is useful quantity from which short circuit KVA or MVA can be easily calculated. In case of fault, maximum MVA that can flow in the cable is transformer rating divided by short circuit impedance.

Profile photo for Jose Soares Augusto

If the transformer is applied to a audio speaker, which connected in the secondary winding, the impedance seen into the transformer at the secondary winding should be similar to that of the speaker. That is impedance matching. It was very important in audio amplifying with vacuum tubes.

If [math]n1[/math] is the number of turns in the primary of the transformer, and [math]n2[/math] the number of secondary turns, then the impedance [math]Z2[/math] seen at the secondary is

[math]Z2=(n2/n1)^2Z_{out}[/math]

where [math]Z_{out}[/math] is the output impedance of the amplifier driving the primary.

Seeing the impedance [math]Z1[/math] in the primary, and if [math]Z_S[/math] is the speaker’s imp

If the transformer is applied to a audio speaker, which connected in the secondary winding, the impedance seen into the transformer at the secondary winding should be similar to that of the speaker. That is impedance matching. It was very important in audio amplifying with vacuum tubes.

If [math]n1[/math] is the number of turns in the primary of the transformer, and [math]n2[/math] the number of secondary turns, then the impedance [math]Z2[/math] seen at the secondary is

[math]Z2=(n2/n1)^2Z_{out}[/math]

where [math]Z_{out}[/math] is the output impedance of the amplifier driving the primary.

Seeing the impedance [math]Z1[/math] in the primary, and if [math]Z_S[/math] is the speaker’s impedance:

[math]Z1=(n1/n2)^2Z_S[/math]

Below is an example. The primary has 180 turns. The secondary, as connected, has 60 turns applied to the speaker (there are several terminals in the auto-transformer to conform to several speaker impedances). The speaker has 1.77 Ohm; the impedance seen at the primary is

[math]Z1=(180/60)^2 * 1.77=9*1.77=15.93\approx 16[/math] Ohm

which is what we need in the primary (see the legend).

In other power transformer applications, such as in power supplies, we are interested usually in voltage levels, which are calculated with the simple ratios [math]n1/n2[/math] or [math]n2/n1[/math], depending on the transformer port we use as the primary.

In these applications, impedance is not important, because the “internal” impedance of a mains connection 220V/50Hz or 110V/60Hz is virtually zero, so the impedance seen at the secondary will be also (almost) zero (copper lines have finite resistance…) and this “zero” is independent of the ratio of the turns.

HTH

It should be percentage impedances on their respective bases should be same. The following explanation may take some time as we go from most simple situation with our imagination until the mathematical proofs for transformers through a series of analysis. And I'm sorry for those quality less photographs being uploaded.

Every practical electrical device has some resistance for dc (electrons traveling in a conducting path are always opposed by static atoms in the material)and some impedance for ac (charge movement is always associated with production of some magnetic field around and if it has ti

It should be percentage impedances on their respective bases should be same. The following explanation may take some time as we go from most simple situation with our imagination until the mathematical proofs for transformers through a series of analysis. And I'm sorry for those quality less photographs being uploaded.

Every practical electrical device has some resistance for dc (electrons traveling in a conducting path are always opposed by static atoms in the material)and some impedance for ac (charge movement is always associated with production of some magnetic field around and if it has time varying in nature this flux opposes its own cause resulting in inductance or reactance (impedance =resistance + j*reactance ; reactance =2πf*inductance))

This resistance or impedance is always considered in series with the source.

Consider two batteries are connected in parallel to feed a single load. In parallel operation the voltages are to be same (to avoid circulating currents).

Case 1: Both the batteries (identical)have same internal resistance then the load current would be shared equally between the two i.e., I1=I2=Il/2.

Case 2: Let R1>R2 then I1<I2 i.e., battery with higher internal resistance feeds less load current. This is a disadvantageous as one battery drains out earlier than the other.

Case 3: Suppose consider a situation where battery1 has higher ampere-hour rating than the battery2. In this condition for both the batteries to drain at the same time battery with higher rating should feed more current than the other matching their proportion to the respective power or ampere-hour ratings. This can be achieved using different internal resistances as shown below

I1/I2 = P1/P2

=> {(E-Vo)/R1}÷{(E-Vo)/R2} = P1/P2

=> R2/R1 = P1/P2

=> R1*P1 = R2*P2

Dividing both sides with voltage sqaure

=>{ R1*P1}÷E^2 = {R2*P2}÷E^2

=> R1 ÷ {E^2/P1} = R2 ÷ {E^2/P2}

=> R1 ÷ (R1 base) = R2 ÷ (R2 base).

=> R1 (pu) = R2 (pu)

Case 4: Two transformers of different rating are operated in parallel.

The above analyses can be related with some considerations.

Note: Electrical devices like transformers should not be operated beyond their rated capacities as their life reduces drastically during that operation.

Suppose transformers with different ratings and different pu impedances are operated in parallel then the transformer with lesser pu impedance may get overloaded much before the set raching their sum of rated capacities. Hence the transformer set is derated (as the combined rating is lesser than the sum of their individual ratings)

Read this case 4 for 3–4 times if you don't understand at once.

Profile photo for Sudhir Sharma

It denotes in % impedance in transformers. E.g. If 11000v / 415 v transformer with 4.5% impedance voltage means from Primary side a 4.5% voltage of 11000v applied & on secondary side RYB shortened & full rated current flow in the transformer. Means 495 Volt applied from Primary side.

% impedance value is more important when multiple transformers has to be paralleled for load caters. All transforme.

It denotes in % impedance in transformers. E.g. If 11000v / 415 v transformer with 4.5% impedance voltage means from Primary side a 4.5% voltage of 11000v applied & on secondary side RYB shortened & full rated current flow in the transformer. Means 495 Volt applied from Primary side.

% impedance value is more important when multiple transformers has to be paralleled for load caters. All transforme...

About · Careers · Privacy · Terms · Contact · Languages · Your Ad Choices · Press ·
© Quora, Inc. 2025